A new customer made contact to ask if I could check their Klargester wastewater treatment unit.
They had noticed an odour recently, and had arranged for it to be emptied. The emptying contractor had advised that the unit wasn't rotating, and kindly suggested contacting me.
I went along and found the motor overload protection for the drive unit was in the off position, and some evidence of carbon dust accumulating on the contactor for the recycle pump.
✅ Carry out electrical and functional tests on the control panel, drive unit, recycle pump, and discharge pump.
✅ Move wiring for the recycle pump on to a previously unused contactor terminal.
✅ Check connections for condition and security.
With satisfactory electrical tests, and functionality tests, no clear reason could be identified as to why the unit had ceased rotating. However, the site voltage was observed as fluctuating between 244 V and 251 V while on site - elevated voltage can result in motors drawing current beyond their rating plate / overload setting, and the drive unit running continuously will be fully exposed to voltage deviations.
Voltages, particularly on rural networks, are seeing reduced stability, and general rise, as energy from solar PV is not only being fed into the network, but properties with solar PV will be reducing demand on the network, which will tend to push voltage upwards.
🛠️⚡💦💩🤠