Three phase motor winding each have a start to the phase and the end to the phase. These phases are then connected in a DELTA or WYE configuration. Any unbalance in test results will show up regardless of the connected configuration. If the test result is to be used as baseline data, any subsequent testing should be done in the same configuration for trending and comparative purposes.
๐ง๐ผ ๐๐ฒ๐๐ ๐๐ต๐ฒ ๐บ๐ผ๐๐ผ๐ฟ ๐ถ๐ป ๐ฎ ๐๐๐๐ง๐ ๐ฐ๐ผ๐ป๐ณ๐ถ๐ด๐๐ฟ๐ฎ๐๐ถ๐ผ๐ป: Firmly connect leads T1 to T12, T2 to T10, T3 to T11, T4 to T7, T5 to T8, and T6 to T9. Then use the pairs containing T1, T2, and T3 as phases 1,2, and 3 for testing.
๐ง๐ผ ๐๐ฒ๐๐ ๐๐ต๐ฒ ๐บ๐ผ๐๐ผ๐ฟ ๐ถ๐ป ๐ฎ ๐ช๐ฌ๐ ๐ฐ๐ผ๐ป๐ณ๐ถ๐ด๐๐ฟ๐ฎ๐๐ถ๐ผ๐ป: Firmly connect and insulate leads T10, T11, and T12.
Then connect leads T4 to T7, T5 to T8, and T6 to T9 and use 1,2, and 3 as phases connections for testing.
For MCA testing the main importance is that all coils get tested during the test and the recommended connections accomplish this. If an unbalance is detected then individual coils can be tested as discussed below. Individual phases or coils can be tested by performing single phase measurements from the start of a phase or coil to the end of the same phase or coil.
For example, in a DELTA connected 12 lead motor, A phase can be measured from 4 to 9, B phase to 5 to 7, and C phase 6 to 8. For a WYE connected motor, A phase 1-10, B phase 2-1, C phase 3-12. Individual segments can be compared using single phase measurements of individual coils, 1-4, 2-5, 3-6, 7-10, 8-11, 9-12.
, , , , , , , , ,