Bay Compliance and Testing

Bay Compliance and Testing Expertise/testing/compliance of ASTs, USTs and product lines at both retail and commercial fueling l

Bay Compliance & Testing Services

Manage your site's annual and triennial testing

Annual line and leak detector testing, including supply and returns to backup generators

Tank testing on ASTs & USTs for any requirement including water ingress, NOV, or insurance purposes

Triennial cathodic protection testing and repairs if needed

Triennial testing of spill containments

Triennial testing of di

spenser and STP containmemts

Pressure decays, including Tank Tie Test

Vent cap testing

A/L testing

Blockage testing

Decommissionings

Annual ATG inspection/recert

Triennial overfill alarm inspection

Triennial overfill prevention inspection

Annual sump inspection

30-day walkthrough inspections

General 10-point inspection

For Sale:2022 Ford F-350 Super Cab173,926 Miles6.2 V8 4x4 Dually Knapheide Enclosed Work Body w/ Ergo Ladder RackAC, Cru...
05/07/2026

For Sale:
2022 Ford F-350 Super Cab
173,926 Miles
6.2 V8 4x4 Dually
Knapheide Enclosed Work Body w/ Ergo Ladder Rack
AC, Cruise Control, Bluetooth.
Can connect to Ford App, for remote start, lock and unlock.
Please message me if you are interested, I will respond as quick as I can.

02/18/2026

Tank with water ingress. Vacuum tank test failing. Pressure decay revealed sources were the STP riser and the ATG cap.

02/18/2026

A tank with water ingress. Pressure decay revealed source was the tank access lid.

10/08/2025

2 gas tanks with water ingress. Pressure decay revealed sources were in both STP sumps.

10/08/2025

Gas tank with water ingress. Pressure decay revealed the source was the vent line.

05/15/2025

Diesel tank with water ingress.
Pressure decay revealed issues with the spill bucket drain plug and the STP manifold.

04/24/2025

Pressure decay failing due to the ATG cap/ring.
Potential location for water ingress.

03/16/2025

Tank with water ingress. Pressure decay revealed sources were the ATG & extractor riser caps.

03/07/2025

Diesel tank with water ingress. Pressure decay revealed the ATG cap/grommet was one of the sources.

03/07/2025

Gas tank with 28+" of phasing/water. Pressure decay revealed the ATG riser was the source.

Address

315 Great Bridge Boulevard, Unit B
Chesapeake, VA
23320

Opening Hours

Monday 8am - 5pm
Tuesday 8am - 5pm
Wednesday 8am - 5pm
Thursday 8am - 5pm
Friday 8am - 5pm

Telephone

+17574105974

Alerts

Be the first to know and let us send you an email when Bay Compliance and Testing posts news and promotions. Your email address will not be used for any other purpose, and you can unsubscribe at any time.

Contact The Business

Send a message to Bay Compliance and Testing:

Share