A dairy farm's solar panels kept getting blamed for cutting the power. The solar wasn't the problem.
Running 23 hours a day, this farm couldn't afford downtime, but kept tripping its main RCD on hot days.
We don't like just fixing the immediate problem, we get down to the root cause.
Do it once, do it right!
After measuring the earth leakage on several different submains, we found the issues.
- one single RCD was protecting the entire site and the accumulation of earth leakage was enough to tip it over the edge
- Incorrectly sized earth bonding causing the building steel work to act as the main earth path.
We split it across several RCDs with a custom panel built to fit, added an alarm to notify the team of faults instantly and also added failsafes to the Solar PV system to prevent it from operating when the onsite generator was in use.
The biggest hurdle? Swapping the system out with only one hour a day downtime, we did it through a well thought out plan.